Eaton (IQ100 series,IQ130,IQ140,IQ150) - логгирование данных. Карта регистров MODBUS.
Данные ниже соответствуют только программе Advanced Serial Data Logger или Advanced TCP/IP Data Logger и могут быть не применимы для других программных продуктов.
Смещение MODBUS | Описание | Ед. изм. | Тип данных |
16 | Meter type | bit-mapped | word |
17 | Firmware version | | string(4) |
19 | Map version | 0 to 65535 | word |
20 | Meter configuration | bit-mapped | word |
21 | Asic version | 0-65535 | word |
899 | Watts, 3 ph сумма | Watt | single |
901 | Vars, 3 ph сумма | VARs | single |
903 | Vas, 3 ph сумма | VAs | single |
999 | Voits A N | voIts | single |
1001 | Voits B N | volts | single |
1003 | Voits C N | voIts | single |
1005 | Voits A B | volts | single |
1007 | Voits B C | volts | single |
1009 | Voits C A | volts | single |
1011 | Амперы A | amps | single |
1013 | Амперы B | amps | single |
1015 | Амперы C | amps | single |
1017 | Watts, 3 ph сумма | watts | single |
1019 | Vars, 3 ph сумма | VARs | single |
1021 | Vas, 3 ph сумма | VAs | single |
1025 | Частота | Hz | single |
1027 | Neutral ток | amps | single |
1099 | W часы, received | Wh | integer |
1101 | W часы, delivered | Wh | integer |
1103 | W часы, net | Wh | integer |
1105 | W часы, сумма | Wh | integer |
1107 | Var часы, positive | VARh | integer |
1109 | Var часы, negative | VARh | integer |
1111 | Var часы, net | VARh | integer |
1113 | Var часы, сумма | VARh | integer |
1115 | Va часы, сумма | 0 to 99999999 | integer |
1999 | Амперы a, average | amps | single |
2001 | Амперы b, average | amps | single |
2003 | Амперы c, average | amps | single |
2005 | Positive watts, 3 ph, average | watts | single |
2007 | Positive vars, 3 ph, average | VARs | single |
2009 | Negative watts, 3 ph, average | watts | single |
2011 | Negative vars, 3 ph, average | VARs | single |
2013 | Vas, 3 ph, average | -9999 M to +9999 M | single |
2015 | Positive pf, 3 ph, average | -1.00 to +1.00 | single |
2017 | Negative pf, 3 pf, average | -1.00 to +1.00 | single |
3001 | Вольтаж B n, minimum | Volt | single |
3129 | Negative коэффициент преобразования мощности, 3 ph, maximum avg demand | -1.00 to +1.00 | single |
4099 | Фаза A ток | -1800 to +1800 | smallint |
4100 | Фаза B ток | -1800 to +1800 | smallint |
4101 | Фаза C ток | -1800 to +1800 | smallint |
4102 | Angle, вольтаж A B | -1800 to +1800 | smallint |
4103 | Angle, вольтаж B C | -1800 to +1800 | smallint |
4104 | Angle, вольтаж C A | -1800 to +1800 | smallint |
4999 | Meter status | bit-mapped | word |
Есть еще ряд значений MODBUS для этого устройства. Их можно посмотреть в программе. |
Eaton (IQ DP 4000) data logging
Eaton (IQ100 series,IQ130,IQ140,IQ150) data logging
Eaton (Power Xpert Meter,PXM 1000) data logging
Eaton (PXM 2000) data logging