1
Source N line neutral l1l0
Volts AC
word
2
Source N line neutral L2 l0
Volts AC
word
3
Source N line neutral l3l0
Volts AC
word
4
Source E line neutral L1 l0
Volts AC
word
5
Source E lineneutral l2l0
Volts AC
word
6
Source E line neutral L3 l0
Volts AC
word
7
Source N line напряжение L1 L2
Volts AC
word
8
Source N line напряжение L2 L3
Volts AC
word
9
Source N line напряжение L3 L1
Volts AC
word
10
Source E line напряжение L1 L2
Volts AC
word
11
Source E line напряжение l2l3
Volts AC
word
12
Source E line напряжение L3 L1
Volts AC
word
13
Source N частота
Hz
word
14
Source E частота
Hz
word
15
Ток L1
Amps
word
16
Ток L2
Amps
word
17
Ток L3
Amps
word
18
Closed transition in фаза degree delta
Degrees
word
38
Closed programmed transition override mode
0 = Auto Override, 1 = Non-Automatic
word
39
Password for writing register 40042
0-32768
word
40
Synchronous напряжение фазовый угол
0-10 degrees
word
41
Synchronous напряжение differential
0%-5%
word
42
Synchronous частота differential
0.0Hz.-0.3Hz.
word
43
Service entrance type
0 = None; 1 = Insulated Case Circuit Breaker, 2 = Molded Case Circuit Breaker, 3 = Contactor
word
44
Фаза rotation actual
0 = disabled; 1 = ABC; 2 = CBA
word
45
Фаза rotation expected
0 = disabled; 1 = ABC; 2 = CBA
word
46
Nominal normal напряжение
Volts AC
word
47
Nominal emergency напряжение
Volts AC
word
48
Nominal normal частота
Hz
word
49
Nominal emergency частота
Hz
word
50
Normal number of фазаs
1 or 3
word
51
Emergency number of фазаs
1 or 3
word
52
Rated amperage
04000
word
57
Password for writing register 40057
0 32768
word
58
Normal engine start time delay
0-10 sec
word
59
Emergency engine start time delay
010 sec
word
60
Normal ext. Engine start time delay
0-3600 sec
word
61
Emergency ext. Engine start time delay
03600 sec
word
62
Normal engine cooldown
0-3600 sec
word
63
Emergency engine cooldown
03600 sec
word
64
Standby to preferred
0-3600 sec
word
65
Preferred to standby
03600 sec
word
66
Off (preferred to standby prog. Transition)
0-3600 sec
word
67
Off (standby to preferred prog. Transition)
03600 sec
word
68
Fail to acquire preferred
1 -3600 sec
word
69
Fail to acquire standby
13600 sec
word
70
Fail to synchronize
1 -3600 sec
word
71
Fail to synch. Enable
0 = disabled; 1 = enabled
word
74
Активная time delay
 
word
75
Активная time delay remaining
Seconds
word
Есть еще ряд значений MODBUS для этого устройства. Их можно посмотреть в программе.